Your position: Home > Medium Voltage Power Cable > 8.7/15(17.5)kV XLPE Insulation Unarmored Power Cable
8.7/15(17.5)kV XLPE Insulation Unarmored Power Cable
8.7/15(17.5)kV XLPE Insulation Unarmored Power Cable
8.7/15(17.5)kV XLPE Insulation Unarmored Power Cable
8.7/15(17.5)kV XLPE Insulation Unarmored Power Cable
8.7/15(17.5)kV XLPE Insulation Unarmored Power Cable
8.7/15(17.5)kV XLPE Insulation Unarmored Power Cable

8.7/15(17.5)kV XLPE Insulation Unarmored Power Cable

To be used for power distribution in medium voltage, as transformer feeders in substations. In power plants, industrial and operation installations...
Certificate :
ISO 9001 ISO 14001 ISO 45001 CE
Manufacturing Capacity :
5000km/Month
Packaging Details :
Wood Drum, Steel-Wood Drum or Metal Drum
Product Description
Product Application
Product Structure
Main Features
Specification
Related Products
Product Description
To be used for power distribution in medium voltage, as transformer feeders in substations. In power plants, industrial and operation installations, in residential areas and mining installations, in dry or wet locations.
Get a Custom Quote
Product Application
To be used for power distribution in medium voltage, as transformer feeders in substations. In power plants, industrial and operation installations, in residential areas and mining installations, in dry or wet locations.
Product Application
Product Application
Product Application
Product Structure
8.7/15(17.5)kV XLPE Insulation Unarmored Power Cable
01
Conductor
- Plain class 2 compacted copper or Aluminum
02
Conductor Screen
- Semi-conductive compound
03
Insulation
- Cross linked polyethylene (XLPE)
04
Insulation Screen
- Semi-conductive compound
05
Metallic Screen
- Plain annealed copper tape
06
Filler
- Non-hygroscopic material(For Three core)
07
Binder Tape
- Non-hygroscopic material tape
08
Outer Sheath
- Polyvinyl chloride compound (PVC)
Standard
Cable design: IEC 60502-2 or custom cable
Conductor: IEC 60228
Voltage Test
AC Voltage Withstand: 3.5U0/5min,No breakdown
Partial discharge test:1.73U0,≯10pc
Temperature Characteristics
Conductor operating temperature: -15℃~90℃
                   Min. temperature laying condition: 0℃
Conductor emergency operating temperature: 105℃
Conductor short-circuit operating temperature (5s): 250℃
Specification

Table 1 Single core CU(AL)/XLPE/CTS/PVC

 

No.
& CSA
Conductor XLPE insulation Copper tape screen Outer sheath Weight kg/km
Approx. diameter mm Nominal thickness mm Nominal thickness mm Nominal thickness mm Diameter mm YJV(CU) YJLV(AL)
1*25 6 4.5 0.12 1.7 21.84 677.8 525.3
1*35 7 4.5 0.12 1.7 22.84 794.8 582.3
1*50 8.2 4.5 0.12 1.7 24.04 939.7 652.3
1*70 10 4.5 0.12 1.8 26.04 1200.2 778.4
1*95 11.6 4.5 0.12 1.9 27.84 1490.1 910.2
1*120 13 4.5 0.12 1.9 29.24 1751.9 1020.8
1*150 14.6 4.5 0.12 2 31.04 2077.4 1165.1
1*185 16.2 4.5 0.12 2 32.64 2452.3 1315
1*240 18.4 4.5 0.12 2.1 35.04 3024 1549.3
1*300 20.6 4.5 0.12 2.2 37.44 3642.7 1799.3
1*400 23.8 4.5 0.12 2.3 40.84 4584.7 2172.6
1*500 26.6 4.5 0.12 2.4 44.08 5651.5 2589.5
1*630 30 4.5 0.12 2.5 47.68 7020.6 3102.5
1*800 34 4.5 0.12 2.6 51.88 8719.3 3732.7

 

Table 2 Three core CU(AL)/XLPE/CTS/PVC

 

No.
& CSA
Conductor XLPE insulation Copper tape screen Outer sheath Weight kg/km
Approx. diameter mm Nominal thickness mm Nominal thickness mm Nominal thickness mm Diameter mm YJV(CU) YJLV(AL)
3*25 6 4.5 0.1 2.4 44.1 2222 1763
3*35 7 4.5 0.1 2.5 46.4 2618 1978
3*50 8.2 4.5 0.1 2.6 49.2 3110 2243
3*70 10 4.5 0.1 2.7 53.3 3939 2667
3*95 11.6 4.5 0.1 2.8 57 4856 3107
3*120 13 4.5 0.1 2.9 60.2 5719 3514
3*150 14.6 4.5 0.1 3 63.9 6749 3998
3*185 16.2 4.5 0.1 3.1 67.5 7969 4540
3*240 18.4 4.5 0.1 3.3 72.7 9808 5362
3*300 20.6 4.5 0.1 3.5 77.8 11792 6234
3*400 23.8 4.5 0.1 3.7 85.1 14816 7543
3*500 26.6 4.5 0.1 3.9 92.1 18229 8997
3*630 30 4.5 0.1 4.1 99.8 22587 10774
3*800 34 4.5 0.1 4.4 109.1 28062 13027
Related Products
To be used for power distribution in medium voltage, as transformer feeders in substations. In power plants, industrial and operation installations, in residential areas and mining installations, in dry or wet locations, fixed installed in air, directly buried in the ground or in ducts, where require higher mechanical protection.