Your position: Home > High Voltage Power Cable > 64/110(125)kV High Voltage XLPE Insulation Power Cable
64/110(125)kV High Voltage XLPE Insulation Power Cable
64/110(125)kV High Voltage XLPE Insulation Power Cable
64/110(125)kV High Voltage XLPE Insulation Power Cable
64/110(125)kV High Voltage XLPE Insulation Power Cable
64/110(125)kV High Voltage XLPE Insulation Power Cable
64/110(125)kV High Voltage XLPE Insulation Power Cable
64/110(125)kV High Voltage XLPE Insulation Power Cable
64/110(125)kV High Voltage XLPE Insulation Power Cable

64/110(125)kV High Voltage XLPE Insulation Power Cable

Product is suitable for transmission and distribution power lines with current of 50Hz, fixed voltage not exceeding 64/110kV...
Certificate :
ISO 9001 ISO 14001 ISO 45001
Manufacturing Capacity :
500km/Month
Packaging Details :
Steel-Wood Drum or Metal Drum
Product Description
Product Application
Product Structure
Main Features
Specification
Related Products
Product Description
Product is suitable for transmission and distribution power lines with current of 50Hz, fixed voltage not exceeding 64/110kV, with general fire protection requirements and external sheath with certain insulation requirements.
Get a Custom Quote
Product Application
Product is suitable for transmission and distribution power lines with current of 50Hz, fixed voltage not exceeding 64/110kV, with general fire protection requirements and external sheath with certain insulation requirements.
Product Application
Product Application
Product Application
Product Structure
64/110(125)kV High Voltage XLPE Insulation Power Cable
01
Conductor
-Circular stranded compacted conductor (≤800mm2), Milliken conductor (>800mm2)
02
Conductor Screen
-Super smooth Semi-conductive compound
03
Insulation
-Super clean Cross linked polyethylene (XLPE)
04
Insulation Screen
-Super smooth Semi-conductive compound
05
Semi
-Conductive bedding: Semi-conductive tape
06
 Metallic Layer
-Corrugated Aluminum sheath or Lead Sheath or Aluminum Laminated Tape
07
Anticorrosive Coating
-Cable asphalt
08
Outer Sheath
-Polyvinyl chloride compound (PVC) or Polyethylene (PE)
09
Conductive Layer
-Graphite
10
Optional
-Copper wire screen, metal wire armored.
Standard
IEC 60840
Voltage Test
AC Voltage Withstand: 2.5U0/30min,No breakdown
Partial discharge test:1.5U0,≯10pc
Temperature Characteristics
Conductor operating temperature: -15℃~90℃  
             Min. temperature laying condition: 0℃
Conductor short-circuit operating temperature (5s): 250℃
Specification

Table 1 CU(AL)/XLPE/CAS/PVC(HDPE)

 

Nominal

CSA

mm2

Approx.

Conductor

diameter

mm

Nominal

Insulation Thickness

mm

Outer Sheath thickness

mm

Approx. Cable diameter

mm

Approx. cable weight

kg/km

CU AL
240 18.4 19.0 4.0 90.4 8214 6813
300 20.6 18.5 4.0 91.6 8863 7083
400 23.4 17.5 4.0 93.4 9628 7408
500 26.6 17.0 4.0 95.6 10776 7857
630 30.0 16.5 4.5 99.0 12512 8660
800 34.0 16.0 4.5 102.0 14324 9355
800(SM) 35.6 16.0 4.5 104.7 14658 9711
1000(SM) 39.7 16.0 4.5 109.4 17211 10979
1200(SM) 42.8 16.0 5.0 113.5 19304 12025
1400(SM) 46.4 16.0 5.0 117.1 21477 12943
1600(SM) 49.2 16.0 5.0 119.9 23533 13822
1800(SM) 51.4 16.0 5.0 121.3 25429 14556
2000(SM) 54.5 16.0 5.0 124.4 27688 15479
2500(SM) 60.9 16.0 5.0 130.8 32792 17515
Related Products
To be used for power distribution in medium voltage, as transformer feeders in substations. In power plants, industrial and operation installations, in residential areas and mining installations, in dry or wet locations, fixed installed in air, directly buried in the ground or in ducts, where require higher mechanical protection.