To be used for power distribution in medium voltage, as transformer feeders in substations. In power plants, industrial and operation installations...
Certificate :
ISO 9001 ISO 14001 ISO 45001 CE
Manufacturing Capacity :
5000km/Month
Packaging Details :
Wood Drum, Steel-Wood Drum or Metal Drum
Product Description
Product Application
Product Structure
Main Features
Specification
Related Products
Product Description
To be used for power distribution in medium voltage, as transformer feeders in substations. In power plants, industrial and operation installations, in residential areas and mining installations, in dry or wet locations.
Get a Custom Quote
Product Application
To be used for power distribution in medium voltage, as transformer feeders in substations. In power plants, industrial and operation installations, in residential areas and mining installations, in dry or wet locations.
Product Application
Product Application
Product Application
Product Structure
3.6/6(7.2)kV XLPE Insulation Unarmored Power Cable
01
Conductor
- Plain class 2 compacted copper or Aluminum
02
Conductor Screen
- Semi-conductive compound
03
Insulation
- Cross linked polyethylene (XLPE)
04
Insulation Screen
- Semi-conductive compound
05
Metallic Screen
- Plain annealed copper tape
06
Filler
- Non-hygroscopic material(For Three core)
07
Binder Tape
- Non-hygroscopic material tape
08
Outer Sheath
- Polyvinyl chloride compound (PVC)
Standard
Cable design: IEC 60502-2 or custom cable
Conductor: IEC 60228
Voltage Test
AC Voltage Withstand: 3.5U0/5min,No breakdown
Partial discharge test:1.73U0,≯10pc
Temperature Characteristics
Conductor operating temperature: -15℃~90℃
                   Min. temperature laying condition: 0℃
Conductor emergency operating temperature: 105℃
Conductor short-circuit operating temperature (5s): 250℃
Specification

Table 1 Single core CU(AL)/XLPE/CTS/PVC

 

No.
& CSA
Conductor XLPE insulation Copper tape screen Outer sheath Weight kg/km
Approx. diameter mm Nominal thickness mm Nominal thickness mm Nominal thickness mm Diameter mm YJV(CU) YJLV(AL)
1*25 6 2.5 0.12 1.5 17.44 516.6 364.1
1*35 7 2.5 0.12 1.6 18.64 635.2 422.7
1*50 8.2 2.5 0.12 1.6 19.84 772.2 484.8
1*70 10 2.5 0.12 1.7 21.84 1019.4 597.6
1*95 11.6 2.5 0.12 1.7 23.44 1286.4 706.5
1*120 13 2.5 0.12 1.8 25.04 1550 818.9
1*150 14.6 2.5 0.12 1.8 26.64 1851 938.7
1*185 16.2 2.5 0.12 1.9 28.44 2228 1090.7
1*240 18.4 2.6 0.12 1.9 30.84 2780.3 1305.6
1*300 20.6 2.8 0.12 2 33.64 3405.4 1562
1*400 23.8 3 0.12 2.2 37.64 4368.6 1956.5
1*500 26.6 3.2 0.12 2.3 41.28 5446.7 2384.7
1*630 30 3.2 0.12 2.4 44.88 6799.7 2881.6
1*800 34 3.2 0.12 2.5 49.08 8479.8 3493.2

 

Table 2 Three core CU(AL)/XLPE/CTS/PVC

 

No.
& CSA
Conductor XLPE insulation Copper tape screen Outer sheath Weight kg/km
Approx. diameter mm Nominal thickness mm Nominal thickness mm Nominal thickness mm Diameter mm YJV(CU) YJLV(AL)
3*25 6 2.5 0.1 2.1 34.8 1651 1191
3*35 7 2.5 0.1 2.2 37.2 2020 1379
3*50 8.2 2.5 0.1 2.3 40 2476 1609
3*70 10 2.5 0.1 2.4 44.1 3252 1981
3*95 11.6 2.5 0.1 2.5 47.7 4117 2368
3*120 13 2.5 0.1 2.6 51 4943 2739
3*150 14.6 2.5 0.1 2.7 54.6 5921 3170
3*185 16.2 2.5 0.1 2.8 58.3 7100 3671
3*240 18.4 2.6 0.1 3 63.9 8910 4464
3*300 20.6 2.8 0.1 3.2 69.9 10919 5361
3*400 23.8 3 0.1 3.5 78.2 13988 6715
3*500 26.6 3.2 0.1 3.7 86.1 17442 8211
3*630 30 3.2 0.1 3.9 93.8 21736 9923
3*800 34 3.2 0.1 4.2 103.1 27133 12098
Related Products
To be used for power distribution in medium voltage, as transformer feeders in substations. In power plants, industrial and operation installations, in residential areas and mining installations, in dry or wet locations, fixed installed in air, directly buried in the ground or in ducts, where require higher mechanical protection.