Your position: Home > Low Voltage Power Cable > 0.6/1kV XLPE Insulation Armored Power Cable
0.6/1kV XLPE Insulation Armored Power Cable
0.6/1kV XLPE Insulation Armored Power Cable
0.6/1kV XLPE Insulation Armored Power Cable
0.6/1kV XLPE Insulation Armored Power Cable

0.6/1kV XLPE Insulation Armored Power Cable

To be used for main power supply such as in low voltage distribution power networks, indoor and outdoor areas. It can be installed in ducts, in dry or wet locations...
Certificate :
ISO 9001 ISO 14001 ISO 45001 CE
Manufacturing Capacity :
5000km/Month
Packaging Details :
Wood Drum, Steel-Wood Drum or Metal Drum
Product Description
Product Application
Product Structure
Main Features
Specification
Related Products
Product Description
To be used for main power supply such as in low voltage distribution power networks, indoor and outdoor areas. It can be installed in ducts, in dry or wet locations, recommended for direct burial where require higher electrical and mechanical protection.
Get a Custom Quote
Product Application
To be used for main power supply such as in low voltage distribution power networks, indoor and outdoor areas. It can be installed in ducts, in dry or wet locations, recommended for direct burial where require higher electrical and mechanical protection.
Product Application
Product Application
Product Application
Product Structure
0.6/1kV XLPE Insulation Armored Power Cable
01
Conductor
- Plain annealed class 2 stranded (compacted) copper
02
Insulation
- Cross linked polyethylene (XLPE)
03
Filler
- Non-hygroscopic material
04
Binder Tape
- Non-hygroscopic material tape
05
Inner Sheath
- Polyvinyl chloride compound (PVC)
06
Armor
- Galvanized steel wires(For multi-core),Aluminum wire(For single core)
07
Binder Tape
- Non-hygroscopic material tape
08
Outer Sheath
- Polyvinyl chloride compound (PVC)
Standard
Cable design: IEC 60502-1 or AS/ZNS 5000.1 or BS 5467 custom cable
Conductor: IEC 60228 or AS/ZNS 1125
Temperature Characteristics
Conductor operating temperature: -15℃~90℃
                   Min. temperature laying condition: 0℃
Conductor emergency operating temperature: 105℃
Conductor short-circuit operating temperature (5s): 250℃
Specification

Table1 Single core CU/XLPE/PVC/AWA/PVC IEC 60502-1

 

No. of cores Approx. diameter of conductor Nominal thickness of insulation Nominal diameter of armor wire Nominal thickness of outer sheath Approx. OD of cable Approx. weight of cable
& CSA
Phase Earth Phase Earth
mm mm mm mm mm mm mm kg/km
1C1.5 1.56 / 0.7 / 0.8 1.4 10 123
1C2.5 2.04 / 0.7 / 0.8 1.4 10.5 140
1C4 2.55 / 0.7 / 0.8 1.4 11 163
1C6 3.1 / 0.7 / 0.8 1.4 11.6 191
1C10 4 / 0.7 / 0.8 1.4 12.5 242
1C16 5 / 0.7 / 0.8 1.4 13.5 313
1C25 6.1 / 0.9 / 0.8 1.4 15 425
1C35 7.2 / 0.9 / 0.8 1.4 16.1 530
1C50 8.4 / 1 / 1.25 1.5 18.6 723
1C70 10 / 1.1 / 1.25 1.5 20.4 951
1C95 12 / 1.1 / 1.25 1.6 22.6 1241
1C120 13 / 1.2 / 1.6 1.7 24.7 1553
1C150 14.9 / 1.4 / 1.6 1.7 27 1868
1C185 16.5 / 1.6 / 1.6 1.8 29.3 2264
1C240 18.4 / 1.7 / 1.6 1.9 31.6 2856
1C300 21 / 1.8 / 1.6 1.9 34.4 3480
1C400 23.4 / 2 / 2 2.1 38.8 4506
1C500 26.6 / 2.2 / 2 2.2 42.6 5632
1C630 30 / 2.4 / 2 2.3 46.6 7049
1C800 34 / 2.6 / 2.5 2.5 52.9 9072

 

Table2 Two core CU/XLPE/PVC/SWA/PVC 60502-1

 

No. of cores Approx. diameter of conductor Nominal thickness of insulation Nominal diameter of armor wire Nominal thickness of outer sheath Approx. OD of cable Approx. weight of cable
& CSA
Phase Earth Phase Earth
mm mm mm mm mm mm mm kg/km
2C1.5 1.56 / 0.7 / 0.8 1.8 14.5 326
2C2.5 2.04 / 0.7 / 0.8 1.8 15.4 378
2C4 2.55 / 0.7 / 0.8 1.8 16.4 440
2C6 3.1 / 0.7 / 0.8 1.8 17.5 513
2C10 4 / 0.7 / 1.25 1.8 20.2 775
2C16 5 / 0.7 / 1.25 1.8 22.2 970
2C25 6.1 / 0.9 / 1.6 1.8 26 1426
2C35 7.2 / 0.9 / 1.6 1.8 28.2 1712
2C50 8.4 / 1 / 1.6 1.8 31 2080
2C70 10 / 1.1 / 1.6 2 35.6 2729
2C95 12 / 1.1 / 2 2.1 41 3763
2C120 13 / 1.2 / 2 2.2 43.6 4405
2C150 14.9 / 1.4 / 2 2.3 48.5 5276
2C185 16.5 / 1.6 / 2.5 2.5 54.3 6780
2C240 18.4 / 1.7 / 2.5 2.7 58.9 8244
2C300 21 / 1.8 / 2.5 2.8 65.2 9986

 

Table3 Three core CU/XLPE/PVC/SWA/PVC 60502-1

 

No. of cores Approx. diameter of conductor Nominal thickness of insulation Nominal diameter of armor wire Nominal thickness of outer sheath Approx. OD of cable Approx. weight of cable
& CSA
Phase Earth Phase Earth
mm mm mm mm mm mm mm kg/km
3C1.5 1.56 / 0.7 / 0.8 1.8 14.9 358
3C2.5 2.04 / 0.7 / 0.8 1.8 16 420
3C4 2.55 / 0.7 / 0.8 1.8 17.1 497
3C6 3.1 / 0.7 / 0.8 1.8 18.3 594
3C10 4 / 0.7 / 1.25 1.8 21.1 900
3C16 5 / 0.7 / 1.25 1.8 23.3 1160
3C25 6.1 / 0.9 / 1.6 1.8 27.3 1708
3C35 7.2 / 0.9 / 1.6 1.8 29.6 2082
3C50 8.4 / 1 / 1.6 1.9 32.9 2594
3C70 10 / 1.1 / 2 2 38.8 3730
3C95 12 / 1.1 / 2 2.2 43.5 4771
3C120 13 / 1.2 / 2 2.3 46.3 5640
3C150 14.9 / 1.4 / 2.5 2.5 53.1 7308
3C185 16.5 / 1.6 / 2.5 2.6 57.7 8679
3C240 18.4 / 1.7 / 2.5 2.8 63.1 10766
3C300 21 / 1.8 / 2.5 3 69.5 13049

 

Table4 Four core CU/XLPE/PVC/SWA/PVC 60502-1

 

No. of cores Approx. diameter of conductor Nominal thickness of insulation Nominal diameter of armor wire Nominal thickness of outer sheath Approx. OD of cable Approx. weight of cable
& CSA
Phase Earth Phase Earth
mm mm mm mm mm mm mm kg/km
4C1.5 1.56 / 0.7 / 0.8 1.8 15.7 400
4C2.5 2.04 / 0.7 / 0.8 1.8 16.9 474
4C4 2.55 / 0.7 / 0.8 1.8 18.1 572
4C6 3.1 / 0.7 / 1.25 1.8 20.4 830
4C10 4 / 0.7 / 1.25 1.8 22.5 1059
4C16 5 / 0.7 / 1.6 1.8 25.7 1514
4C25 6.1 / 0.9 / 1.6 1.8 29.3 2046
4C35 7.2 / 0.9 / 1.6 1.9 32.2 2545
4C50 8.4 / 1 / 1.6 2 35.8 3181
4C70 10 / 1.1 / 2 2.2 42.4 4594
4C95 12 / 1.1 / 2 2.3 47.4 5875
4C120 13 / 1.2 / 2.5 2.5 52.2 7523
4C150 14.9 / 1.4 / 2.5 2.6 58 9055
4C185 16.5 / 1.6 / 2.5 2.8 63.3 10811
4C240 18.4 / 1.7 / 2.5 3 69.2 13502
4C300 21 / 1.8 / 2.5 3.2 76.4 16386

 

Table5 Five core CU/XLPE/PVC/SWA/PVC 60502-1

 

No. of cores Approx. diameter of conductor Nominal thickness of insulation Nominal diameter of armor wire Nominal thickness of outer sheath Approx. OD of cable Approx. weight of cable
& CSA
Phase Earth Phase Earth
mm mm mm mm mm mm mm kg/km
5C1.5 1.56 / 0.7 / 0.8 1.8 16.6 443
5C2.5 2.04 / 0.7 / 0.8 1.8 17.9 534
5C4 2.55 / 0.7 / 1.25 1.8 20.2 783
5C6 3.1 / 0.7 / 1.25 1.8 21.6 942
5C10 4 / 0.7 / 1.25 1.8 24.1 1213
5C16 5 / 0.7 / 1.6 1.8 27.5 1747
5C25 6.1 / 0.9 / 1.6 1.8 31.6 2393
5C35 7.2 / 0.9 / 1.6 1.9 34.7 3005
5C50 8.4 / 1 / 2 2.1 40.2 4110
5C70 10 / 1.1 / 2 2.3 46 5462
5C95 12 / 1.1 / 2.5 2.4 53 7540
5C120 13 / 1.2 / 2.5 2.6 56.7 8975
5C150 14.9 / 1.4 / 2.5 2.8 63.4 10872
5C185 16.5 / 1.6 / 2.5 3 69.6 13139
5C240 18.4 / 1.7 / 2.5 3.2 75.7 16346
5C300 21 / 1.8 / 3.15 3.4 85.4 20899
Related Products
To be used for power distribution in medium voltage, as transformer feeders in substations. In power plants, industrial and operation installations, in residential areas and mining installations, in dry or wet locations, fixed installed in air, directly buried in the ground or in ducts, where require higher mechanical protection.