The products applies to the lines of 0.6/1kv, aerial insulated cable for overhead power distribution lines, admissible long-term operating temperature for conductor of cable for  XLPE insulation, not exceed 90℃.
Certificate :
ISO 9001 ISO 14001 ISO 45001
Manufacturing Capacity :
5000km/Month
Packaging Details :
Wood Drum, Steel-Wood Drum or Metal Drum
Product Description
Product Application
Product Structure
Main Features
Specification
Related Products
Product Description
The products applies to the lines of 0.6/1kv, aerial insulated cable for overhead power distribution lines, admissible long-term operating temperature for conductor of cable for  XLPE insulation, not exceed 90℃.
Get a Custom Quote
Product Application
The products applies to the lines of 0.6/1kv, aerial insulated cable for overhead power distribution lines, admissible long-term operating temperature for conductor of cable for  XLPE insulation, not exceed 90℃.
Product Application
Product Application
Product Application
Product Structure
The products is also called insulated ABC Cable, suitable for aluminum core or aluminum alloy core weatherproof XLPE insulated overhead cable under AC rated voltage of 1kv in overhead power line. 0.6/1kV Aerial Insulated Cable consists of Aluminum, Aluminum alloy Core, XLPE Insulation. The neutral messengers can be concentrically stranded AAC, or aluminum alloy. The phase core are manufactured with ridges for phase identification(one with one ridge, one with two ridges ,one is plain) or other request.
Aerial Bunched Cable
Standard
IEC standard, ICEA standard, AS/NZS standard,SANS standard ,NF C standard ,and customizable cable.
Feature
Overhead, UV, Economic Design, Best Suited for distribution line.
Specification

Table1 NF C33-209

 

Phase Core Neutral Core Street Lighting Core Complete Cable
No.
and
Section
Area
No.
of
Wire
Dia. of
Conductor
(Approx.)
Insulation
Thickness
No.
and
Section
Area
No.
of
Wire
Dia. of
Conductor
(Approx.)
Insulation
Thickness
  No.

  and
Section

  area
No.
of
Wires
Diameter
   of
conductor
Insulation
Thickness
Overall
Diameter
(Approx.)
Weight
(Approx.)
mm2 No. mm mm mm2 No. mm mm mm2 No. mm mm mm kg/km
2×16 7 4.8 1.2 14.2 126
2×25 7 6.0 1.4 176 194
2×35 7 70 1.6 20.4 266
2×50 7 8.1 1.6 22.6 341
4×16 7 4.8 1.2 17.2 252
4×25 7 6.0 1.4 21.2 388
4×35 7 70 1.6 24.6 533
3×25 7 6.0 1.4 1×54.6 7 9.45 1.6 23.6 496
3×25 7 6.0 1.4 1×54.6 7 9.45 1.6 1×16 7 4.8 1.2 24.9 560
3×25 7 6.0 1.4 1×54.6 7 9.45 1.6   2×16 7 4.8 1.2 26.6 624
3×35 7 70 1.6 1×54.6 7 9.45 1.6 26.1 604
3×35 7 70 1.6 1×54.6 7 9.45 1.6   1×16 7 4.8 1.2 27.2 668
3×35 7 70 1.6 1×54.6 7 9.45 1.6   2×16 7 4.8 1.2 28.7 732
3×50 7 8.1 1.6 1×54.6 7 9.45 1.6 28.1 716
3×50 7 8.1 1.6 1×54.6 7 9.45 1.6  1×16 7 4.8 1.2 28.9 780
3×50 7 8.1 1.6 1×54.6 7 9.45 1.6   2×16 7 4.8 1.2 30.3 844
3×70 12 10.0 1.8 1×54.6 7 9.45 1.6 32.2 940
3×70 12 10.0 1.8 1×54.6 7 9.45 1.6 1×16 7 4.8 1.2 32.7 1004
3×70 12 10.0 1.8 1×54.6 7 9.45 1.6   2×16 7 4.8 1.2 33.8 1068
3×70 12 10.0 1.8 1×54.6 7 9.45 1.6 1×25 7 6.0 1.4 33.6 1038
3×70 12 10.0 1.8 1×54.6 7 9.45 1.6   2×25 7 6.0 1.4 35.5 1137
3×70 12 10.0 1.8 1×70 7 10.20 1.5 32.1 970
3×70 12 10.0 1.8 1×70 7 10.20 1.5  1×16 7 4.8 1.2 32.5 1035
3×70 12 10.0 1.8 1×70 7 10.20 1.5   2×16 7 4.8 1.2 33.6 1099
3×95 19 11.7 1.8 1×70 7 10.20 1.5 35.6 1212
3×95 19 11.7 1.8 1×70 7 10.20 1.5   1×16 7 4.8 1.2 35.7 1276
3×95 19 11.7 1.8 1×70 7 10.20 1.5   2×16 7 4.8 1.2 36.6 1340
3×120 19 13.0 1.8 1×70 7 10.20 1.5 38.0 1439
3×120 19 13.0 1.8 1×70 7 10.20 1.5   1×16 7 4.8 1.2 378 1503
3×120 19 13.0 1.8 1×70 7 10.20 1.5   2×16 7 4.8 1.2 38.6 1567
3×150 19 14.4 1.7 1×70 7 10.20 1.5 40.2 1650
3×150 19 14.4 1.7 1×70 7 10.20 1.5   1×16 7 4.8 1.2 39.8 1714
3×150 19 14.4 1.7 1×70 7 10.20 1.5   2×16 7 4.8 1.2 40.4 1778
3×120 19 13.0 1.8 1×95   19 12.50 1.6 39.5 1526
3×120 19 13.0 1.8 1×95   19 12.50 1.6 1×16 7 4.8 1.2 39.5 1590
3×120 19 13.0 1.8 1×95   19 12.50 1.6   2×16 7 4.8 1.2 39.8 1654
3×150 19 14.4 1.7 1×95   19 12.50 1.6 41.7 1736
3×150 19 14.4 1.7 1×95   19 12.50 1.6  1×16 7 4.8 1.2 41.7 1800
3×150 19 14.4 1.7 1×95   19 12.50 1.6   2×16 7 4.8 1.2 41.6 1865

 

 

Related Products
To be used for power distribution in medium voltage, as transformer feeders in substations. In power plants, industrial and operation installations, in residential areas and mining installations, in dry or wet locations, fixed installed in air, directly buried in the ground or in ducts, where require higher mechanical protection.