Your position: Home > High Voltage Power Cable > 76/132(145)kV High Voltage XLPE Insulation Power Cable
76/132(145)kV High Voltage XLPE Insulation Power Cable
76/132(145)kV High Voltage XLPE Insulation Power Cable
76/132(145)kV High Voltage XLPE Insulation Power Cable
76/132(145)kV High Voltage XLPE Insulation Power Cable
76/132(145)kV High Voltage XLPE Insulation Power Cable
76/132(145)kV High Voltage XLPE Insulation Power Cable
76/132(145)kV High Voltage XLPE Insulation Power Cable
76/132(145)kV High Voltage XLPE Insulation Power Cable

76/132(145)kV High Voltage XLPE Insulation Power Cable

Product is suitable for transmission and distribution power lines with current of 50Hz, fixed voltage not exceeding 76/132kV…
Certificate :
ISO 9001 ISO 14001 ISO 45001
Manufacturing Capacity :
500km/Month
Packaging Details :
Steel-Wood Drum or Metal Drum
Product Description
Product Application
Product Structure
Main Features
Specification
Related Products
Product Description
Product is suitable for transmission and distribution power lines with current of 50Hz, fixed voltage not exceeding 76/132kV, with general fire protection requirements and external sheath with certain insulation requirements.
Get a Custom Quote
Product Application
Product is suitable for transmission and distribution power lines with current of 50Hz, fixed voltage not exceeding 76/132kV, with general fire protection requirements and external sheath with certain insulation requirements.
Product Application
Product Application
Product Application
Product Structure
76/132(145)kV High Voltage XLPE Insulation Power Cable
01
Conductor
-Circular stranded compacted conductor (≤800mm2), Milliken conductor (>800mm2)
02
Conductor Screen
-Super smooth Semi-conductive compound
03
Insulation
-Super clean Cross linked polyethylene (XLPE)
04
Insulation Screen
-Super smooth Semi-conductive compound
05
Semi
-Conductive bedding: Semi-conductive tape
06
 Metallic Layer
-Corrugated Aluminum sheath or Lead Sheath or Aluminum Laminated Tape
07
Anticorrosive Coating
-Cable asphalt
08
Outer Sheath
-Polyvinyl chloride compound (PVC) or Polyethylene (PE)
09
Conductive Layer
-Graphite
10
Optional
-Copper wire screen, metal wire armored.
Standard
IEC 60840
Voltage Test
AC Voltage Withstand: 2.5U0/30min,No breakdown
Partial discharge test:1.5U0,≯10pc
Temperature Characteristics
Conductor operating temperature: -15℃~90℃ 
Min. temperature laying condition: 0℃
Conductor short-circuit operating temperature (5s): 250℃
Specification

Table 1 CU/XLPE/CAS/PVC(HDPE)

 

Nominal CSA mm2 Approx.Conductor diameter mm Nominal Insulation Thickness mm Approx. Cable diameter mm Approx. cable weight kg/km CU
300 20.6 18 88.6 7900
400 23.4 18 91.5 8920
500 26.6 18 95 10200
630 30 18 99.3 11900
800 34 18 103 13900
1000(SM ) 39.7 18 109.4 18000
1200(SM) 42.8 18 113.4 20200
1600(SM) 49.2 18 120.3 24700
2000(SM) 54.5 18 125.6 27200
Related Products
To be used for power distribution in medium voltage, as transformer feeders in substations. In power plants, industrial and operation installations, in residential areas and mining installations, in dry or wet locations, fixed installed in air, directly buried in the ground or in ducts, where require higher mechanical protection.